Overview
The i90 Scanner provides an interface between Bailey Network 90® IO and a Logix system using multiple EtherNet/IP class 1 connections. The i90 Scanner supports up to 34 Bailey® IOmodules and consumes 7 Logix IO connections.
The i90 Scanner provides an interface between Bailey INFI 90® I/O and a Logix system using multiple EtherNet/IP class 1 connections. Each i90 Scanner supports up to 34 Bailey® I/O modules and consumes 7 Logix IO connections.
The i90 Scanner is configured using the free Aparian Slate application which can be downloaded here.
Within the Slate environment each i90 I/O module can be configured to match the application.
The following IO modules have been tested and are supported:
- IMASI02/NASI02 – 15 Channel Analog Input
- IMDSI02/NDSI02 – 16 Channel Digital Input
- IMDSO04/NDSO04 – 16 Channel Digital Output
- IMASO01/NASO01 – 14 Channel Analog Output
- IMDSM05/NDSM05 – 2 x 8 Channel Digital Input/Output
- IMCIS02/NCIS02 – Combination IO (4 Channel Analog Input, 2 Channel Analog Output, 3 Channel Digital Input, 4 Channel Digital Output)
As additional I/O modules become available to Aparian, they will be tested and supported.
Using the EDS AOP (Add-On-Profile) in Studio 5000, the i90 Scanner can be added directly into the Logix IO tree. AOIs (Add-On-Instructions) are provided for both Standalone and Redundant architectures and facilitate the mapping of IO and diagnostic information to meaningful (UDT) tag structures.
In the case of a redundant system, the AOI also automatically switches between the Active and Standby i90 Scanner.
To aid in migration, the i90 Scanner provides a Shadow mode, where the i90 Scanner can run in parallel with the existing Bailey processor. In this mode the existing CPU is controlling the IO modules and the i90 Scanner is listening-in and providing the input and output readback data to the Logix controller.
The i90 Scanner hosts two Ethernet ports which can either be used as an unmanaged switch or used in a Device-Level-Ring (DLR) topology, providing Ethernet redundancy.
The i90 Scanner has a range of diagnostics, statistics, and tools to support the user during the migration process. This will speed up fault finding and reduce down-time.
Application
Standalone mode, Linear Ethernet, Single Logix Controller

Redundant mode, Linear Ethernet, Single Logix Controller

Redundant mode, Ring Ethernet, Single Logix Controllers

Redundant Mode, Ring Ethernet, Redundant Logix Controller

Multiple Chassis, Linear Ethernet, Single Logix Controller

Specification
Electrical
Specification |
Rating |
Power requirements |
5V DC,540 mA (derived from INFI 90® MMU) |
Power Consumption |
2.7 W |
Emissions |
IEC61000-6-4 |
ESD Immunity |
EN 61000-4-2 |
Radiated RF Immunity |
IEC 61000-4-3 |
EFT/B Immunity |
EFT: IEC 61000-4-4 |
Surge Immunity |
Surge: IEC 61000-4-5 |
Conducted RF Immunity |
IEC 61000-4-6 |
Environmental
Specification |
Rating |
Mounting |
Occupies single slot in standard INFI 90® MMU |
Temperature |
-20 to 70°C |
Air Quality |
Non-corrosive |
Ethernet
Specification |
Rating |
Connector |
RJ45 |
Conductors |
CAT5 STP/UTP |
ARP connections |
Max 40 |
TCP connections |
Max 40 |
CIP connections |
Max 10 |
Communication rate |
10/100Mbps |
Duplex mode |
Full/Half |
Auto-MDIX support |
Yes |
Controller Support |
ControlLogix, CompactLogix, MicroLogix, SLC |
Embedded Switch |
Yes, 2 x Ethernet ports Supports DLR (Device-Level-Ring) and Linear topology |
Certifications
Specification |
Rating |
CE Mark |
 |
RoHS3 Compliant |
 |
Downloads
Documents
Size : 4.24 MB
Type : PDF
Size : 554.47 KB
Type : PDF
Size : 1.13 MB
Type : PDF
Size : 1.24 MB
Type : PDF
Examples
Size : 178.64 KB
Type : L5X
Size : 198.38 KB
Type : L5X
EDS Files
Size : 5.13 KB
Type : EDS
Add On Profile - AOP
Firmware