CANBus Router
A-CANBR/B
The CAN Bus Router provides intelligent data routing between either EtherNet/IP or Modbus TCP/RTU and a CAN Bus network. This allows the user to integrate CAN Bus devices into a Rockwell Automation Logix platform (e.g., ControlLogix or CompactLogix) or any Modbus Client or Server device with minimal effort.
- Receive up to 100 pre-configured CAN Bus packets.
- Send up to 100 pre-configured CAN Bus packets.
- CAN Bus transmission can be scheduled (periodic), or externally triggered, sent on Start-up, or any combination of these.
- Logix L5X generation - Ready for import
- Supports Passthrough Messaging from Logix
- Module has various Primary Interfaces:
- EtherNet/IP Target (Class 1 connection)
- Modbus Server (TCP, RTU232, and RTU485)
- Modbus Client (TCP, RTU232, and RTU485)
- EtherNet/IP Originator (Class 1 connection with up to 10 EtherNet/IP devices and Explicit Messaging, including Direct-To-Tag Logix tag access, with up to 10 EtherNet/IP devices).
- Slate software provides a CAN Bus and Modbus packet capture utility for better diagnosis of communication issues.
- Supports common CAN Bus Baud Rates (10k, 20k, 50k, 125k, 250k, 500k, 800k, 1M)
- Dual Ethernet ports which support Device-Level-Ring (DLR).
- Network Time Protocol (NTP) supported for external time synchronization.
- Small form factor – DIN rail mounted.
Overview
The module supports one of four Primary Interface modes:
EtherNet/IP Target
Here a remote EtherNet/IP device (e.g. a Logix controller) establishes a number of Class 1 connections to the module. CAN Bus data can be mapped between the input and output class 1 cyclic connections of the Logix controller (allowing up to 2KB input and 2KB output to be exchanged at the requested packet interval – RPI).
EtherNet/IP Originator
As an EtherNet/IP originator, the module can use one of three methods to read and write data to and from the CAN Bus network:
- EtherNet/IP Explicit Messaging
This allows CAN Bus devices to exchange data with up to 10 EtherNet/IP devices. The module can use either Class 3 or Unconnected Messaging (UCMM) to Get and Set data in the remote EtherNet/IP devices.
- Direct-To-Tag technology
This allows the CAN Bus devices to exchange data with a Logix controller without the need to write any application code (e.g. ladder) in Studio 5000. The CAN Bus data is directly read from, or written to, Logix tags.
- EtherNet/IP Class 1 connection
CAN Bus data can be mapped to a maximum of 10 EtherNet/IP devices using input and output class 1 cyclic connections. This will allow the CAN Bus Router to “own” the EtherNet/IP target device and exchange CAN Bus data using the EtherNet/IP device’s input and output assemblies.
Modbus Server
The diagnostics and CAN Bus data will be written to, or read from, the module’s internal Modbus Registers (Holding or Input Registers). These registers can be accessed by a remote Modbus Client using either Modbus TCP, Modbus RTU232, or Modbus RTU485.
Modbus Client
The diagnostics and CAN Bus data will be written to, or read from, the module’s internal Modbus Registers (Holding or Input Registers). The Modbus Auxiliary Map can then be used to configure the Modbus data exchange between multiple remote Modbus Server devices and the module’s internal Modbus registers. The Modbus communication can be via Modbus TCP, Modbus RTU232, or Modbus RTU485.
When configured as an EtherNet/IP Target, the software can generate an L5X file which can be imported into Studio 5000. This provides all the necessary UDTs, Tags and mapping ladder to allow the Logix application code to easily access the CAN Bus data.
The CAN Bus Router is configured using the Aparian Slate application. This program can be downloaded from www.aparian.com free of charge.
The module also provides a range of statistics, CAN Bus and Modbus packet capture functions, and internal Modbus and Data table reads to simplify remote diagnosis.
The module has two Ethernet ports and supports Device-Level-Ring (DLR) architectures.
A built-in webserver provides detailed diagnostics of system configuration and operation, including the display of CAN Bus operation and communication statistics, without the need for any additional software.
Application
The figures below provide an example of the typical network setup for connecting CAN Bus devices to either EtherNet/IP or Modbus TCP/RTU232/RTU485.
Example of connecting CAN Bus sensors to a Logix Controller:

Example of connecting EtherNet/IP drives to a CAN Bus network:

Example of connecting CAN Bus devices to a Modbus TCP Client or Server:

Specification
Electrical
| Specification | Rating |
| Power requirements | Input: 10 – 32V DC |
| Power consumption | 2.2 W (Max) Current:180 mA @ 10 V Current:85 mA @ 24 V |
| Connector | 3-way terminal, 5.08mm pitch |
| Conductors | 24 – 18 AWG |
| Enclosure rating | IP20, NEMA/UL Open Type |
| Temperature | -20 – 70 °C |
| Earth connection | Yes, terminal based |
| Emissions | IEC61000-6-4 |
| ESD Immunity | EN 61000-4-2 |
| Radiated RF Immunity | IEC 61000-4-3 |
| EFT/B Immunity | EFT: IEC 61000-4-4 |
| Surge Immunity | Surge: IEC 61000-4-5 |
| Conducted RF Immunity | IEC 61000-4-6 |
Ethernet
| Specification | Rating |
| Connector | RJ45 |
| Conductors | CAT5 STP/UTP |
| ARP connections | Max 200 |
| TCP connections | Max 200 |
| CIP connections | Max 15 |
| Communication rate | 10/100Mbps |
| Duplex mode | Full/Half |
| Auto-MDIX support | Yes |
| Embedded Switch | Yes, 2 x Ethernet ports |
| Device Level Ring (DLR) | Supported |
| Network Time Protocol (NTP) | Supported |
Serial Port (RS232)
| Specification | Rating |
| Connector | 9-way terminal (shared with RS485) |
| Conductor | 24 – 18 AWG |
| Electrical Isolation | 1000 Vdc |
| BAUD | 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 |
| Parity | None, Even, Odd |
| Data bits | 8 |
| Stop bits | 1 |
Serial Port (RS485)
| Specification | Rating |
| Connector | 9-way terminal (shared with RS232) |
| Conductor | 24 – 18 AWG |
| Electrical Isolation | 1500 Vrms for 1 minute |
| BAUD | 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 |
| Parity | None, Even, Odd |
| Data bits | 8 |
| Stop bits | 1 |
CAN Bus
| Specification | Rating |
| Connector | 5-way terminal, 5.08mm pitch. |
| Max CAN Receive Items | 100 |
| Max CAN Send Items | 100 |
| Passthrough Messaging | Supported |
| Supported BAUD Rates | 10k, 20k, 50k, 125k, 250k, 500k, 800k, 1M |
| CAN Terminator | 120 Ω - Software Enabled |
EtherNet/IP Target
| Specification | Rating |
| Class 1 Cyclic Connection Count | 4 |
| Logix Direct-to-Tag Supported | Yes |
EtherNet/IP Originator
| Specification | Rating |
| Class 1 Cyclic Connections Supported | Yes |
| Class 3 / UCMM Connections Supported | Yes |
| Class 1 Connection Count | 10 |
| Class 3 / UCMM Target Device Count | 10 |
| Class 3 / UCMM Mapping Count | 50 |
Modbus Client
| Specification | Rating |
| Modes Supported | Modbus TCP, Modbus RTU2232, Modbus RTU485 |
| Modbus RTU485 Termination | 125 Ω - Software Enabled |
| Max Modbus Slave Devices | 20 |
| Max Modbus Mappings | 100 |
| Mapping Ranges | Holding Register 0 – 65535 Input Register 0 – 65535 Input Status 0 – 65535, Coil Status 0 – 65535 |
| Base Offset | Modbus (Base 0) PLC (Base 1) |
| Configurable Modbus TCP Port | Yes |
| Data Reformatting Supported | BB AA BB AA DD CC CC DD AA BB DD CC BB AA |
Modbus Server
| Specification | Rating |
| Modes Supported | Modbus TCP, Modbus RTU2232, Modbus RTU485(simultaneously) |
| Modbus RTU485 Termination | 125 Ω - Software Enabled |
| Mapping Ranges | Holding Register 0 – 65535 Input Register 0 – 65535 Input Status 0 – 65535, Coil Status 0 – 65535 |
| Base Offset |
Modbus (Base 0) PLC (Base 1) |
| Configurable Modbus TCP Port | Yes |
Certifications
| Specification | Rating |
| CE Mark | ![]() |
|
UL Listed FILE: E494895 |
CLASS 1, DIV 2, GROUPS A, B, C, D
|
| ODVA Conformance | ![]() |
| RoHS3 Compliant | ![]() |
Dimensions

Downloads
Documents
Examples
EDS Files
Firmware